heaters. To minimize the risk of
drawing these lethal gases back into
the home, please follow the heating
equipment manufacturers safety
standards and guidelines. Refer to
NFPA and ASHRAE for additional
information.
Duct Run Calculation
The maximum duct run before
effecting the performance of the
hood is 100’. Calculate your duct run
by measuring linear feet and adding
the elbows, transitions and caps
Maximum Run
6” or 3 1/4 x 10” duct 100 FT
Deduct
Each 90 elbow used 15FT
Each 45 elbow used 9FT
Each 6” or 3 1/4 x 10” duct
Transition used 1FT
Each 3’1/4 x 10” to 6”
Transition used 5FT
Side Wall with damper 30FT
Roof Cap 30FT
2
E L E C T R I C A L
WARNING: All electrical work must
be performed by a qualified
electrician.
Please ensure that the appropriate
electrical codes or prevailing local
building codes and ordinances are
adhered to.
Ensure that the electricity supply is
disconnected at source. Do not use
an extension cord or adapter plug
with this appliance.
This appliance must be grounded.
Connect to a properly grounded
branch circuit, protected by a 15
amp circuit breaker.
Electrical Supply
This appliance requires 120V/60Hz,
3amp electrical supply ensure an
appropriately qualified person
completes the electrical hook-up.
The connection point for the
electrical supply is at the top of the
unit, therefore the electrical supply
must be run down from the ceiling
alongside the ductwork.
All electrical and venting hook-ups
must be in place before commencing
installation of the hood-fan.
based on the table below.
block off an area of at least 12”x12”
between the ceiling joists using
2x4’s. Allow for a hole through the
center of this blocking of at least 6”
in diameter through which to pass
the ductwork and electrical cable.
The underside of the hood must not
be closer than 30” from the cook-top
I N S T A L L A T I O N
Structural Preparation for the
Hood Fan Installation
T h e i s l a n d h o o d w e i g h s
approximately 125 lbs. It is therefore
imperative that a substantial
structure is prepared in the ceiling to
attach the range hood to. Ideally
Page view 4